Rack-mounted liquid CDU for high-density server direct-to-chip liquid cooling
This rack-mounted liquid-cooled CDU cools high-density servers via direct-to-chip cold plates, available in 4U/6U/8U/12U rack sizes. Compact and space-saving, it avoids dedicated cooling rooms with short, low-resistance piping for easy modular scaling without system downtime.
It features redundant pumps, dual power, leak and anti-condensation protection, stainless steel pipelines and precision filters. Supporting Modbus, TCP and UDP, it integrates with monitoring systems. Ideal for AI, HPC, edge data centers and labs as a reliable liquid cooling solution.
| Rated Heat Transfer | 30–150kW |
| Rack Mount Size | Standard 4U/6U/8U/12U rack-mounted |
| Primary Side | Cooling water; Inlet/outlet temperature: 35/45℃ |
| Secondary Side | Pure water/PG25; Temperature range: 20–50℃ |
| Circulating Flow Rate | 2.8–14m³/h |
| Total Head | 15m |
| Max Working Pressure | 5Bar |
| Rated Electric Power | 0.7–3kW |
| Communication Protocol | Modbus, TCP, UDP |
| Installation | Built-in IT rack, cabinet-level deployment |
Standard 4U–12U form factor saves space and eliminates dedicated mechanical rooms—fits directly into IT cabinets.
Cabinet-level modularization allows CDU capacity expansion with new racks, supporting incremental growth without system disruption.
Redundant pumps, dual power, leak detection, and anti-condensation logic ensure continuous, fail-safe operation.
Stainless steel piping with precision filtration; supports Modbus/TCP/UDP for easy monitoring and integration.
Tell us your needs for data center infrastructure, and our team will provide you with customized green & energy-saving integrated solutions with global delivery and fast response.